Stabilizer Model: PSS1A
Following checks and corrections are applied during Validation and AutoCorrection.
- If 0.0 < T2 < 0.125*Mult*TimeStep then T2 = 0.0
ElseIf 0.125*Mult*TimeStep < T2 < 0.25*Mult*TimeStep then T2 = 0.25*Mult*TimeStep - If 0.0 < T4 < 0.125*Mult*TimeStep then T4 = 0.0
ElseIf 0.125*Mult*TimeStep < T4 < 0.25*Mult*TimeStep then T4 = 0.25*Mult*TimeStep - If 0 < T6 < Mult*TimeStep then T6 = Mult*TimeStep
- If 0 < T5 < Mult*TimeStep then T5 = Mult*TimeStep
- If Vcl < Vcu then swap the values
- If Lsmax < Lsmin then swap the values. If Lsmax < 0 then Lsmax change sign to positive. If Lsmin > 0 then change sign to negative.
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Model Equations and/or Block Diagrams
Parameters:
| Ics | Stabilizer input code |
| A1 | Notch filter parameters |
| A2 | Notch filter parameters |
| T1 | Lead/lag time constant, sec |
| T2 | Lead/lag time constant, sec |
| T3 | Lead/lag time constant, sec |
| T4 | Lead/lag time constant, sec |
| T5 | Wahsout numerator time constant, sec |
| T6 | Washout denominator time constant, sec |
| Ks | Stabilizer gains |
| Lsmax | Maximum stabilizer output, pu |
| Lsmin | Minimum stabilizer output, pu |
| Vcu | Stabilizer input cutoff threshold, pu |
| Vcl | Stabilizer input cutoff threshold, pu |